Block fazokontrolny FC-75 for the control of phases in a three-phase motor drive control pointer circuits. Unit monitors the presence of the phase currents in the conditions according to GOST 15150 U3.1, but for operation at temperatures from minus 10 ° C to plus 40 ° C and relative humidity of 98% at a temperature of 25 ° C.
Block FC-75 has a plug-in coupling is mounted on the relay cabinets and cupboards.
DC voltage lockout (Ub) at the time of passage of the primary windings of transformers unit three-phase 50 Hz and residual DC voltage (Uost.) arising at open circuit one of the AC phase, measured at the output terminals at a load of (1200 ± 60) ohms are given in table.
Characteristics |
||
Operating current (Ip), A |
Tension lock (Ub), B |
Residual voltage (Uost.), Not more |
1.0 |
16 ± 6 |
1.5 |
3.0 |
30 ± 6 |
1.5 |
5.0 |
36 ± 8 |
1.5 |
Block FC-75 is covered with a plastic transparent cover to prevent accidental contact with live parts and allows to inspect the internal parts without removing the casing.
Block FC-75 has a degree of protection from environmental effects IP50 corresponding group according to GOST 14254.
Block FC-75 according to the method of protection against electric shock class 0 corresponds to GOST 12.2.007.0.
Overall block dimensions, not more 200'87'112